DigiTOP VP-16Af voltage relay is designed to protect electrical devices and household appliances from excessive line voltage.
The relay operates in maximum voltage relay mode and protects electrical equipment from excessive line voltage (can be used to connect an additional consumer in a photovoltaic installation).
The device monitors the upper voltage limit. If this voltage limit is exceeded, the load is switched off (or an additional load can be connected to the power take-off). The load is automatically switched on (off) as soon as the voltage drops to the upper voltage limit minus the voltage drop (hysteresis) after the set response time. That is, if the upper limit is set to 253 V and the hysteresis is 10 V, the load will be turned off when 253 V is exceeded, and if it drops to 243 V, the load will be turned on after the set response time (from 0 to 10 seconds).
Lowering the voltage at a photovoltaic installation is important for safety and efficiency reasons.
Excessive voltage can cause surges and damage to the installation and connected equipment. Surges can arise when there is a sudden increase in power or decrease in resistance in a circuit. Too high a voltage can also increase the risk of electrocution.
It is important to adjust the voltage of the photovoltaic system to the requirements of the equipment and network to which it will be connected.
Programmable settings:
– Upper shutdown limit , step 1V – 230-270V
– Voltage hysteresis (voltage drop from upper limit), step 1V – 1-10V
– Switch-on response time, step 1 sec – 0-10 sec
Single-phase
Rated load current: 10A
Maximum load current: 16A
Operating voltage: 50-400V AC
Network operating frequency: 50Hz
Shutdown time: 0.02 sec.
Contact configuration: changeover contact (NO+NC)
Size: 2 modules on DIN rail